Model: 1735
Portable three phase power logger designed for energy monitoring and load studies. Large graphical display for instant viewing of results and easy on-screen setup. Ships complete with switchable-range 3000A flexible current transformers and software.
Discontinued!
This product has been discontinued and is no longer available.
This is the direct replacement:
The Fluke 1735 Power Logger is the ideal electrician or technician's power meter for conducting energy studies and basic power quality logging. Set the Power Logger up in seconds with the included flexible current probes and color display. The power quality meter measures most electrical power parameters, harmonics, and captures voltage events.
Designed to measure the most critical three-phase power parameters, the 1735 can log rms voltage, rms current, phase angle, voltage events, voltage and current THD, voltage and current harmonics up to the 50th, active power, reactive power, power factor, active energy, reactive energy, and more. With memory for up to 45 days of data, the 1735 can uncover intermittent or hard-to-find issues.
The four current probes are connected with one plug, the instrument automatically detects, scales and powers the probes. These variable range current probes are easily set to 15 A, 150 A, or 3000 A for high accuracy in nearly any application. The voltage connections are single leads, enabling easy and quick setups. The color screen provides instant confirmation that connections are correct, and then logging begins when you press the RECORD button.
Designed to quickly view recorded data, the included Power Log software displays all recorded parameters on interactive trends. Generate a professional report with the 'Report Writer' function, or copy and paste images into report document manually.
Conduct load studies for up to 45 days and view saved data on-screen or on a computer.
Quantify energy consumption quickly on-screen or log to memory for extended periods.
Assess voltage and current harmonics up to the 50th.
Capture voltage events using user-defined thresholds.
View waveforms onscreen to uncover waveform distortion and to verify correct voltage and current connections.
Display | ¼ VGA Graphic Color transmissive displays 320 x 240 Pixel with additional background lighting and adjustable contrast, text and graphics in color |
Quality | Developed, designed and manufactured according to DIN ISO 9001 |
Memory | 4 MB Flash memory, 3.5 MB for measuring data |
Interface | RS-232 SUB-D socket; 115.2 k Baud, 8 data bits, no parity, 1 stop bit, firmware updates are possible with the RS- 232 interface (9-pole extension cable) |
Sample rate | 10.24 kHz |
Line frequency | 50 Hz or 60 Hz, user-selectable, with automatic synchronization |
Power supply | NiMH battery-pack, with ac adapter (15 V to 20 V/0.8 A) |
Operation time with battery | Typical > 12 hours without backlight and > 6 hours with backlight high |
Dimensions | 240 mm x 180 mm x 110 mm |
Weight | 1.7 kg, including battery |
Working temperature range | -10 °C to +50 °C |
Storage temperature range | -20 °C to +60 °C |
Operating temperature range | 0 °C to +40 °C |
Reference temperature range | 23 °C ± 2 °C |
Note | The above terms are defined in European Standards. To calculate the specification at any point in the working temperature range, use the temperature coefficient below. |
Temperature coefficient | ± 0.1 % of the measured value per °C from the reference |
Intrinsic error | Refers to reference temperature, maximum deviation is guaranteed for two years |
Operating error | Refers to operating temperature range, maximum deviation is guaranteed for two years |
Climatic class | C1 (IEC 654-1) -5 °C to +45 °C, 5% to 95% RH, no dew |
Housing | Cycoloy shock and scratch proof thermoplast V0-type (non-flammable) with rubber protection holster |
Emission | IEC/EN 61326-1:1997 class B |
Immunity | IEC/EN 61326-1:1997 |
Safety | IEC 61010-1 600 V CAT III, double or reinforced insulation, pollution degree 2 |
Protection | IP65; EN60529 (refers only to the main housing without the battery compartment) |
RMS values are measured with a 20 ms resolution. |
Measuring range | 57 V/66 V/110 V/120 V/127 V/220 V/230 V/240 V/260 V/277 V/347 V/380 V/400 V/417 V/480 V ac |
Intrinsic error | ± (0.2% of measured value + 5 digits) |
Operating error | ± (0.5% of m. v. + 10 digit) |
Resolution | 0.1 V |
Measuring range | 100 V/115 V/190 V/208 V/220 V/380 V/400 V/415 V/450 V/480 V/600 V/660 V/690 V/720 V/830 V ac |
Intrinsic error | ± (0.2% of m. v. + 5 digit) |
Operating error | ± (0.5 % of m. v. + 10 digit) |
Resolution | 0.1 V |
Flexi set I ranges | 15 A/150 A/3000 A rms (at sine) |
Current clamp ranges | 1 A/10 A |
Resolution | 0.01 A |
Ranges | 150 A/3000 A and 1 A/10 A |
Intrinsic error | ± (0.5 % of m. v. + 10 digit) |
Operating error | ± (1 % of m. v. + 10 digit) |
Ranges | 15 A |
Intrinsic error | ± (0.5 % of m. v. + 20 digit) |
Operating error | ± (1 % of m. v. + 20 digit) |
The errors of the current probes are not considered. |
Flexi Set measuring error | ± (2% of m. v. + 10 digit) |
Position influence | ± (3 % of m. v. + 10 digit) |
CF (typical) | 2.83 |
Note | When using Flexi Set please make sure to position the conductor opposite to the Flexi Set-lock |
Measuring range | see V rms and A rms measurement |
Power errors are calculated by adding the errors of voltage and current | |
Additional error due to power factor PF | |
Specified error x (1-[PF]) | |
Maximum range with voltage range 830 V delta-connection and 3000 A current range is 2.490 MW, higher displayed values possible when using PTs and CTs with ratio feature | |
Intrinsic error | ± (0.7 % of m.v. +15 digit) |
Resolution | 1 kW |
Operating error | ± (1.5 % of m.v. + 20 digit) |
Typical range with voltage range 230 V wye connection and 150 A current range is 34.50 KW. | |
Intrinsic error | ± (0.7 % of m.v. +15 digit) |
Resolution | 1 W to 10 W |
Operating error | ± (1.5 % of m.v. + 20 digit) |
The errors of the current sensors themselves have not been considered. |
Intrinsic error | ± (0.7 % of m.v.+ F variation error* + 15 digit) |
Resolution | 1 W to 10 W |
Operating error | ± (1.5 % of m.v. + F variation error* + 20 digit) |
*Frequency variation error |
Range | 0.000 to 1.000 |
Resolution | 0.001 |
Accuracy | ±1 % of full scale |
Measuring range | 46 Hz to 54 Hz and 56 Hz to 64 Hz |
Intrinsic error | ± (0.2 % of m. v. + 5 digit) |
Operating error | ± (0.5 % of m. v.+ 10 digit) |
Resolution | 0.01 Hz |
Measuring range | To 50th harmonic (< 50 % of nom) |
Vm, Im, THDV, THDI | IEC 61000-4-7:2002, Class II |
Vm > 3% Vn | ± 5% Vm |
Vm < 3 % Vnom | ±0.15% Vnom |
Im > 10 % Inom | ± 5% Im |
Im < 10 % Inom | ± 0 5% Inom |
THDV | for THD < 3% ± 0.15% at Vnom for THD > 3% ± 5% at Vnom |
THDI | for THD < 10% ± 0.5% at Inom for THD > 10% ± 5% at Inom |
Vnom | Normal voltage range |
Inom | Nominal current range |
Vm and Im are measured values of harmonic m |
Detection of voltage dips, voltage swells and voltage interruptions with a 10 ms resolution and measuring error of the half period sine wave of rms. | |
Intrinsic error | ± (1% of m.v. + 10 digit) |
Operating error | ± (2% of m.v. + 10 digit) |
Resolution | 0.1 V |