Home » Accessories » Miscellaneous » Fluke 1555 Kit Insulation Resistance Tester Kit
Fluke 1555 Kit Insulation Resistance Tester Kit
- 10kV 1555 Insulation Resistance Tester
- IP67 Hard Carrying Case
- Large Ruggedized Alligator Clips
- Certificate of Calibration
Part Number:
FE 1555/KIT
In Stock?
Yes! Available up to 2 units Quantity
Price:
$5199.95
USD (change)
Shipping Information:
Ships in 1 - 3 Days
Arrives:
Arrives:
Feb 13-
Feb 19
Max of 2 unitsFeb 19
$0.00 or FREE
for orders of $199
for orders of $199
Fast: Ships tomorrow*
Arrives:
Arrives:
Feb 10
Max of 2 units
$250.00
Fastest: Overnight
Arrives:
Arrives:
Feb 09
Max of 2 units
$338.00




The new Fluke 1555/Kit insulation resistance tester offers digital insulation testing up to 10 kV, making it ideal for testing a wide range of high voltage equipment including switchgear, motors, generators and cables.
Fluke insulation testers can now conduct the entire range of test voltages specified in IEEE 43-2000 with a best in class, 3 year warranty and CAT IV 600 V safety rating. With measurement storage and PC interface, the 1555 is a perfect tool for preventative or predictive maintenance programs designed to identify potential equipment failures before they occur.
What's Included:
Fluke insulation testers can now conduct the entire range of test voltages specified in IEEE 43-2000 with a best in class, 3 year warranty and CAT IV 600 V safety rating. With measurement storage and PC interface, the 1555 is a perfect tool for preventative or predictive maintenance programs designed to identify potential equipment failures before they occur.
Additional Accessories
In addition to the standard accessories that already come with the Fluke 1555, the Fluke 1555/Kit includes:- IP67 hard carrying case
- Ruggedized Alligator clips
- Certificate of calibration
What's Included:
- IP67 hard carrying case
- Ruggedized Alligator clips
- Certificate of calibration
- Test cables with alligator clips (red, black, green)
- Infrared adapter with interface cable
- FlukeView Forms basic CD-ROM
- AC power cord
- Users manual on CD-ROM
- Quick Reference card
- English manual
- USB-IR cable installation guide
- FlukeView Forms installation guide
The Good:
The Bad:
The Bottom Line:
The Bad:
The Bottom Line:
Full Review
- Test voltages up to 10 kV provides solutions for all applications
- CAT III 1000 V, CAT IV 600 V safety rating
- Voltage breakdown detection alerts the user that voltage is present and gives the voltage reading up to 600 V ac or dc for increased user safety
- Selectable test voltages in 50 V steps from 250 to 1000 V, and 100 V steps above 1000 V
- Measurements can be stored in up to 99 memory locations, with each location assigned a unique, user defined, label for easy recall
- Long battery life gives the user over 750 tests between charges
- Automatic calculation of Dielectric Absorption (DAR) and Polarization Index (PI) with no additional setup
- Guard system eliminates the effect of surface leakage current on high-resistance measurements
- Large digital/analog LCD for easy viewing
- Capacitance and leakage current measurement
- Ramp function for breakdown testing
- Resistance measurements up to 2TΩ
- Timer settings up to 99 minutes for timed tests
- 3-year warranty
The Fluke 1555's accuracy is specified for one year after calibration at
operating temperatures of 0 °C to 35 °C. For operating temperatures
outside the range (-20 °C to 0 °C and 35 °C to 50 °C), add ± .25 % per
°C, except on the 20 % bands add ± 1 % per °C.
| Insulation
Resistance Measurement | ||
| Test voltage (DC) | Range (DC) | Accuracy (± reading) |
| 250 V | < 200 kΩ 200 kΩ to 5 GΩ 5 GΩ to 50 GΩ > 50 GΩ | unspecified 5 % 20 % unspecified |
| 500 V | < 200 kΩ 200 kΩ to 10 GΩ 10 GΩ to 100 GΩ > 100 GΩ | unspecified 5 % 20 % unspecified |
| 1000 V | < 200 kΩ 200 kΩ to 20 GΩ 20 GΩ to 200 GΩ > 200 GΩ | unspecified 5 % 20 % unspecified |
| 2500 V | < 200 kΩ 200 kΩ to 50 GΩ 50 GΩ to 500 GΩ > 500 GΩ | unspecified 5 % 20 % unspecified |
| 5000 V | < 200 kΩ 200 kΩ to 100 GΩ 100 GΩ to 1 TΩ > 1 TΩ | unspecified 5 % 20 % unspecified |
| 10000 V | < 200 kΩ 200 kΩ to 200 GΩ 10 GΩ to 2 TΩ > 2 TΩ | unspecified 5 % 20 % unspecified |
| Bar graph range | 0 to 1 TΩ | |
| Insulation test voltage
accuracy | -0
%, +10 % at 1 mA load current | |
| Induced ac mains current rejection | 2 mA maximum | |
| Charging rate for capacitive
load | 5
seconds per μF | |
| Discharge rate for capacitive load | 1.5 s/μF | |
| Range | Accuracy | |
| Leakage current measurement | 1 nA to 2 mA | ± (5 % + 2 nA) |
| Capacitance measurement | 0.01 uF to 15.00 μF | ± (15 % rdg + 0.03 μF) |
| Timer | 0 to 99 minutes | Resolution Setting: 1 minute Indication: 1 second |
| Live
circuit warning | Warning
range 30 V to 660 V ac/dc, 50/60 Hz | Voltage accuracy ± (15 % + 2 V) |
| General
Specifications | ||
| Display | 75 mm x 105 mm | |
| Power | 12 V lead-acid rechargeable battery, Yuasa NP2.8-12 | |
| Charger Input (AC) | 85 V ac 50/60 Hz 20
VA | |
| This Class II (double insulated) instrument is supplied with a
Class 1 (grounded) power cord. The protective earth terminal (ground
pin) is not connected internally. The extra pin is for added plug
retention only. | ||
| Dimensions | 170 mm x 242 mm x 330 mm (6.7 in x 9.5 in x 13 in) | |
| Weight | 3.6 kg (7.94 lb) | |
| Temperature (operating) | -20 ºC to 50 ºC (-4
ºF to 122 ºF) | |
| Temperature (storage) | -20 ºC to 65 ºC (-4 ºF to 149 ºF) | |
| Humidity | 80 % to 31 ºC
decreasing linearly to 50 % at 50 ºC | |
| Altitude | 2000 m | |
| Enclosure sealing | IP40 | |
| Input overload protection | 1000 V ac | |
| Electromagnetic compatibility | EN 61326 | |
| Certifications | CSA CE, TUV-SUD | |
| Safety compliance | CAT III 1000 V, CAT
IV 600 V | |
| Pollution
degree | 2 | |